UPS Runtime Calculator
Find how long your UPS will keep a boiler, router or PC running, and what battery you need.
Add a device (typical power)
If only VA is known, multiply it by the power factor from the label (often 0.6–0.9).
At this load a lead-acid battery delivers about 93 % of its rated capacity (Peukert effect).
You need about 86 Ah at 12 V in total.
How it is calculated
E = V × Ah × n
P_battery = load ÷ efficiency
Runtime = 20 × (E ÷ (P_battery × 20))k
Notation
- V, Ah, n
- battery voltage, capacity and count
- k
- Peukert exponent: 1.1 for AGM and gel, 1 for LiFePO4
- 20
- rated discharge time of lead-acid capacity, hours
Worked example
- Battery 12 V 100 Ah, AGM; load 100 W; efficiency 85%.
- E = 12 × 100 = 1,200 Wh; P_battery = 100 ÷ 0.85 = 117.6 W.
- 1,200 ÷ (117.6 × 20) = 0.510; 0.5101.1 = 0.477.
- 20 × 0.477 = 9.54 h, about 9 h 32 min.
Battery energy equals voltage × amp-hours × number of batteries, but not all of it reaches your devices. The inverter loses 10–20%, and a lead-acid battery gives less than its rated capacity when discharged faster than in 20 hours. The calculator applies both corrections.
The second field works the other way round: enter the hours you need and get the battery capacity.
Ad
Discover your destiny!Tarot MagicTarot card readingsStart Reading ✦Frequently Asked Questions
How long will a UPS with a 12 V 100 Ah battery run?
With a 100 W load and 85% inverter efficiency, about 9 hours 32 minutes on an AGM battery. A LiFePO4 battery of the same capacity lasts about 10 hours 12 minutes.
How long will a small UPS with a 7 Ah battery last?
A typical 12 V 7 Ah battery keeps a 60 W load running for about 54 minutes. At high loads the lead-acid battery delivers only about three quarters of its rated capacity.
What is the Peukert effect?
The faster a lead-acid battery is discharged, the less total energy it delivers. Its Ah rating is usually given for a 20-hour discharge; we use a Peukert exponent of 1.1, typical for AGM batteries.
How do I convert VA to watts?
Multiply VA by the power factor. A 1000 VA UPS with a factor of 0.6 delivers at most 600 W. The VA rating limits power, while runtime depends on the battery.